Data record tests.dielectric-withstand.equipment.switch-open-hv.acceptance
Verified 2026-10-29 Confidence: High
Dielectric Withstand is specified for open medium-voltage and high-voltage air switches in acceptance testing at clause 7.5.1.3.B.5 of ANSI/NETA ATS-2025. The clause calls for a dielectric withstand voltage test on each pole with the switch closed, each pole to ground with the other poles grounded, at the manufacturer's test voltage.
Value: open medium-voltage and high-voltage air switches
| Step | Item | Detail |
|---|---|---|
| Source | ANSI/NETA ATS-2025 | Licensed standard, clause 7.5.1.3.B.5 |
| Data record | tests.dielectric-withstand.equipment.switch-open-hv.acceptance | Verified 2026-10-29 |
| Entry | Dielectric Withstand | No revisions |
- Subject
- Dielectric Withstand (Test methods)
- Kind
- Equipment fact
- Source
- ANSI/NETA ATS-2025, clause 7.5.1.3.B.5, Acceptance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA ATS-2025Publisher information page
- Also stated in
- FIST 4-7, section 6.1.52, page 143 (August 2023).
Read the reference passage
6.1.52 Substation (High Voltage)
"The applied voltage for the high voltage test will depend on the system voltage and will be determined as recommended by the equipment supplier. The high voltage test is typically done for one minute."
FIST 4-7, section 6.1.52, page 143, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- FIST 4-7, section 6.1.52, page 143 (August 2023).
History
| Date | Change |
|---|---|
| 2026-10-29 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.dielectric-withstand.equipment.switch-open-hv.acceptance." Switchgear Testing Reference. 2026-10-29. https://www.switchgeartestingreference.com/data/tests.dielectric-withstand.equipment.switch-open-hv.acceptance/.
Switchgear Testing Reference, Data record tests.dielectric-withstand.equipment.switch-open-hv.acceptance (Oct. 29, 2026), https://www.switchgeartestingreference.com/data/tests.dielectric-withstand.equipment.switch-open-hv.acceptance/.
@misc{etr-data-tests-dielectric-withstand-equipment-switch-open-hv-acceptance,
title = {Data record tests.dielectric-withstand.equipment.switch-open-hv.acceptance},
howpublished = {\url{https://www.switchgeartestingreference.com/data/tests.dielectric-withstand.equipment.switch-open-hv.acceptance/}},
organization = {Switchgear Testing Reference},
publisher = {Switchgear Testing Reference},
year = {2026},
note = {last substantive change 2026-10-29}
}{{cite web |title=Data record tests.dielectric-withstand.equipment.switch-open-hv.acceptance |website=Switchgear Testing Reference |publisher=Switchgear Testing Reference |url=https://www.switchgeartestingreference.com/data/tests.dielectric-withstand.equipment.switch-open-hv.acceptance/ |date=2026-10-29 |access-date=}}